How many receptacles are required around a general care patient bed?
How many receptacles are required around a general care patient bed?
eight receptacles
Each patient bed location shall be provided with a minimum of eight receptacles. They shall be permitted to be of the single, duplex, or quadruplex type or any combination of the three. All receptacles shall be listed “hospital grade” and shall be so identified.
Are not covered by Article 517 health care facilities?
It does not apply to business offices, corridors, waiting rooms, and the like in clinics, medical and dental offices, outpatient facilities, or areas used exclusively for immunizations, psychiatry and psychotherapy, alternative medicine or optometry.
Where is hospital grade MC needed?
Where Is Hospital Grade Mc Required? Clinical and medical units for patients are arranged in Branch circuits in hospitals, nursing facilities, outpatient locations (other than emergency, life safety, or critical care centers).
What makes a hospital grade receptacle hospital grade?
In addition to complying with the general use receptacle Listing requirements, hospital grade receptacles incorporate additional construction features and are subjected to additional performance requirements. These include grounding reliability, assembly integrity, strength and durability tests.
What does green dot on outlet mean?
hospital-grade
The green dots indicate that the UPS outlets and plug are certified as hospital-grade and may be used within patient-care vicinities.
What does an orange receptacle mean?
isolated ground receptacles
According to an information article by Scott Spyrka @spyrkaelectric.com, the orange outlets are isolated ground receptacles that can provide electricity directly from a grounding point, meaning they maintain power even if the circuit breaker is tripped or power is interrupted elsewhere.
How many receptacles are required in an operating room?
36 receptacles
Section 517.19(C) requires each operating room in a critical care area to be provided with at least 36 receptacles. Of these, at least 12 must be connected to either the normal system branch circuit or a critical branch circuit supplied by a different transfer switch than the other receptacles at the same location.
Which type of facility must have a Type 2 EES?
Critical care (Category 1) spaces shall only be served by a Type 2 EES.
Is MC cable allowed in hospitals?
The short answer is yes; certain types of MC cable are suitable for use as a wiring method in patient-care areas. Let’s take a more in-depth look at the Code rules. The requirements for patient-care area branch-circuit equipment grounding conductors are provided in NEC sections 517.13(A) and (B).
Can MC cable be used for emergency circuits?
The simple answer is no. MC cable is not permitted to be used for the emergency lighting system wiring as described in the question. This article provides the reasoning and National Electrical Code (NEC) justification to support the answer. A few fundamentals must be reviewed to provide a thorough response.
What does a green dot on a receptacle mean?
The green dots indicate that the UPS outlets and plug are certified as hospital-grade and may be used within patient-care vicinities. TECHNICAL SUPPORT.
Why are hospital receptacles upside down?
All that holds a faceplate in position is one short screw for an AC receptacle. If the screw loosens and falls out, the faceplate will drop down and short out the two power prongs on anything that is plugged into that outlet. Such accidents used to be commonplace which is why power receptacles were put in upside down.