What is the mounting height of a fire alarm annunciator?

2.1. Fire Alarm Control Units and Remote Annunciators – Display and/or operating controls shall not be more than 72”above the finished floor level.

Where should a fire alarm annunciator panel be located?

The remote annunciator must be located at or near the staff area and be accessible by staff. A remote annunciator located in another room or area of the facility, or behind a door that can be closed or locked, does not meet the condition that the staff area must have “fire alarm annunciation.”

How high should a fire alarm panel be mounted?

The operable part of the manual stations shall be installed not less than 3 ½ ft. (42″) and not more than 4 ft. (46”) to center above finished floor. All pull stations shall be installed at the same height throughout the facility.

Where do I put FACP?

The FACP is to be located on the first floor. The top of the FACP or annunciator panels shall be mounted sixty (60) inches to seventy-two (72) inches above finished floor unless specifically approved by the Fire Code Official (See DIAGRAM F-5.1).

What is an annunciator panel on a fire alarm?

Fire alarm panel The annunciator panel will indicate the zone and approximate physical location of the source of a fire alarm in the building. The annunciator will also include lamps and audible warning devices to indicate failures of alarm circuits.

What is the height of a fire alarm pull station?

Manual Fire Alarm Boxes (Pull Stations) – The height of the manual fire alarm boxes shall be a minimum of 42 inches and a maximum of 54 inches measured vertically, from the floor level to the activating handle or lever of the box.

What is the standard height of panel board?

5 feet, 4 inches
The actual panelboard height is 5 feet, 4 inches, but it is mounted 20 inches from the floor. The top of the panelboard is 84 inches (7 feet) above the floor.

Which device is used in annunciator panel?

Process alarm switches may be used to trigger a special type of indicator device known as an annunciator. An annunciator is an array of indicator lights and associated circuitry designed to secure a human operator’s attention by blinking and sounding an audible buzzer when a process changes into an abnormal state.

What is an annunciator panel in building?

An annunciator panel is a group of lights used as a central indicator of status of equipment or systems in an industrial process, building or other installation.